Installation Instructions
Du ct---F ree Sys tems
Coo ling Only and Heat Pump Units
Low Ambient Temperature Contr ol Accessor y
NOTE: Read and become familiar with these instructions before
beginning installation.
SAFETY CONSIDERATIONS
Installing and servicing air--conditioning equipment can be
hazardous due to system pressures and electrical components. Only
trained and qualified personnel should install or service
air-- conditioning equipment. When working on air-- conditioning
equipment, observe the precautions provided in literature, tags, and
labels attached to the unit.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes and
National Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety--alert symbol
!
!
.
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand these signal words: DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury o r death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury
or death.
Before beginning any modification or installation of this kit,
be sure the main electrical disconnect is in the OFF position.
Ensure power is disconnected to the fan coil unit. On some
systems both the fan coil and the outdoor unit may be on the
same disconnect. T ag the disconnect switch with a suitable
warning label. There may be more than one disconnect.
!
WARNING
GENERAL
IMPORTANT: Heat pump models require an isolation relay and
fieldwiringtopreventfancyclinginheatpumpmode.SeeTable1
for isolation relay part numbers.
Table 1 Isolation Relay Part Numbers
Models
RCD
Part No.
Voltage
38MVQ009/012 P283---0291 120v
38MVQ012 P283---0292 240v
38MVQ018/024 P283---0292 240v
38QRR/QRF P283---0293 24v
538B_R/538Q_R P283---0293 24v
Wind baffles are required for low ambient operation. For 38HD,
38QR and 538B models, the baffles are a factory accessory (see
Table 2 for part numbers). For 38MVC and 38MVQ models, the
baffles are field fabricated using factory drawings (see Table 2 for
drawing numbers).
Table 2 Wind Baffle Accessories for R --410A Units
Models Wind Baffle Part No.
38HDF/QRF/HDR/QRR018
538E_F/538Q_F018
5 3 D S --- 9 0 0 --- --- --- 0 7 0
38HDF/38HDR024, 38HDF030,
38QRF/38QRR024
538E_F/538A_R024
538E_F030
538Q_F/538B_R024
5 3 D S --- 9 0 0 --- --- --- 0 8 7
38HDF036/38QRF030/035/036,
38HDR/38QRR030/036
538E_F036
538Q_F030/035/036,
538A_R/538B_R030/036
5 3 D S --- 9 0 0 --- --- --- 0 7 1
38HDR/QRR048,060
538A_R/538B_R048,060
5 3 D S --- 9 0 0 --- --- --- 0 8 8
Models
Wind Baffle Drawing
No.*
38MVC/38MVQ009 5 3 D S --- 9 0 0 --- --- --- 0 9 7
38MVC/38MVQ012 5 3 D S --- 9 0 0 --- --- --- 0 9 7
38MVC/38MVQ018 5 3 D S --- 9 0 0 --- --- --- 0 9 8
38MVC/38MVQ024 5 3 D S --- 9 0 0 --- --- --- 0 9 9
*Drawings available on HVAC Partners.