Installation Instructions
TIME- - DELAY
RELAY KIT
NOTE: Read the entire instruction before beginning the
installation.
INTRODUCTION
The Time-- Delay Relay permits the indoor fan to briefly continue
to operate and provide additional cooling after the compressor
cycles off.
SAFETY CONSIDERATIONS
Installing and servicing air conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained personnel should install or service air conditioning
equipment.
Untrained personnel can perform basic maintenance functions,
such as cleaning coils and cleaning and replacing filters. All other
operations should be performed by trained service personnel.
When working on air conditioning equipment, observe
precautions in the literature, and on tags and labels attached to the
unit.
Follow all safety codes. Wear safety glasses and work gloves. Use
a quenching cloth for brazing operations. Have a fire extinguisher
available.
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before beginning any modification be sure the main
electrical disconnect is in the OFF position. TAG SWITCH
WITH A SUITABLE WARNING LABEL.
!
WARNING
INSTALLATION
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in personal injury.
Before installing this kit, be sure high-- and low--voltage
electrical power to indoor section is disconnected.
CAUTION
!
1. Using screws provided, mount time--delay relay to fan coil
or furnace cabinet. Position time--delay relay in convenient
place so that wires will be close to connection point. Drill
0.125 in. (use 1/8 drill size) screw holes into cabinet.
NOTE: Check to make sure no components inside cabinet are
within drilling range.
2. Paint edges of screw holes to resist rust. Install mounting
screws through time-- delay relay and into screw holes.
Tighten screws securely but do not overtighten.
ELECTRICAL OPERATION HAZARD
Failure to follow this caution may result in personal injury
or equipment damage.
The time--delay relay and low-- voltage wiring should be
physically separated from high-- voltage components and
wiring.
CAUTION
!
3. Refer to Fig. 1 for wiring connections.
4. Connect red wire from time--delay relay to terminal R on
low--voltage terminal board in fan coil or furnace.
5. Connect brown wire from time-- delay relay to terminal C
on low--voltage terminal board.
6. Splice wire from thermostat terminal G to black wire from
time--delay relay.
7. Connect orange wire from time--delay relay to terminal G
on low--voltage terminal board.
8. Affix wiring label next to indoor unit wiring label.
9. Check all connections. Turn on electrical power.
10. Affix caution label on indoor unit access panel to electrical
controls.
11. To check function of system, set thermostat to operate in
cooling mode. With system “calling for cooling” run for
minimum of 5 minutes, then slowly move cooling lever
on thermostat to higher setting to satisfy thermostat. Once
the thermostat is satisfied, the indoor fan will continue to
run approximately 90 seconds, then shut off.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment
damage.
This accessory package includes an adhesive--backed
warning sticker. Affix this sticker prominently to fan coil or
furnace after installation.
CAUTION
!